L20 DOORS / SHUTTERS / HATCHES
Escalator Fire Shutters
A
range of lateral rolling shutters designed to prevent the spread of fire or
maintain security between floors in areas representing a fire risk such as
shopping centres, hotels and large commercial properties. The shutters are
designed to protect escalators as well as stairwells and can also be designed to
protect glazed atriums with a horizontal shutter at each fire compartment
level.
Dimensions:
Shutter length up to 6.5 metres - Coil box size:
1100 x 900mm.
Shutter length 6.5-8 metres - Coil box size: 1200 x
1000mm.
Shutter length 8-10 metres - Coil box size: 1300 x
1100mm.
Standard shutter width: up to 5000mm.
Drive Housing
12mm
mild steel endplates with rolled steel angles to form an enclosed box which
contains the drive roller and drive mechanism. Clad in fire resistant metal
sheet with removable inspection covers for maintenance. The shutter coil box and
side guides should be clad with decorative material after
installation.
Curtain
105mm galvanised interlocking flat lath
sections, each alternate lath secured both ends by steel end locks to drive the
arrangement. Leading edge constructed from rolled steel angles with rollers for
smooth operation.
Side Guides
Fabricated from mild steel,
incorporating side restraints to maintain curtain position. The guides, if
required, can be contoured to harmonize in with installation
design.
Finish
The shutter curtain is supplied bright spangled
galvanised. All other components are protected by rust inhibiting primer paint.
Additional finishes are available on request.
Electrical
Standard
voltage: 415V, 3 phase, 50 Hz. The electrical equipment can be rated to suit the
power supply available. The supply should be provided by others and terminated
in a switched isolator box next to the coil box housing. The motor position can
be handed to suit the site conditions. A control panel is provided which is
usually installed outside the coil box housing which typically will include the
following features as standard:
Open, close and stop buttons.
Key switch
test facility.
Connection facility to the building fire alarm system,
typically requiring a normally open/normal closed volt free dry contact
connection.
An audible warning of the shutter
closing.
Safety
The following features are provided as
standard:
Audible warning of the opening and closing of the
shutter.
Variable time delay prior to closing.
Infrared photo safety beam
designed to stop the shutter if the beam is broken for a pre-set delay prior to
fully closing.
Options
Battery standby
Battery backup or
alternative powered systems to the standard range are available. Where a battery
operated system is provided, the battery system should normally be housed within
the control panel enclosure. The power output should give a minimum of 3
open/close operations. Full details are available from Northern Doors design
office on request.
Balustrade/Side Walls
The side guides are fixed
to a fire resistant structure of equal or greater fire resistance to that of the
shutter. The structure may be formed from a variety of materials but can be
formed as either part of the building structure or steel, clad in an approved
fire resistant material. Full details are available from Northern Doors design
office on request.
Fire Resistance
To BS 476: Part 22, Section 8: 4
hours stability and integrity (tested by the Loss Prevention Council). LPCP
Approved and certified.
Consult with Northern Doors (UK) Ltd technical
literature for details. Northern Doors can also provide a design and
specification advisory service and it is recommended that they are consulted
early in the design process.
Manufacturer: Northern Doors (UK) Ltd, Kingsforth
Road, Thurcroft, Rotherham, South Yorkshire, S66 9HU. Tel: 01709 545 999. Fax:
01709 545 341. Email:
This email address is being protected from spam bots, you need Javascript enabled to view it
Web: www.northerndoors.co.uk
Product reference: Escalator Fire Shutters
Performance:
Fire resistance: 4 hours
stability and integrity
Arrangement: Lateral rolling shutters
Shutter curtain: 105mm galvanised interlocking
flat lath sections, each alternate lath secured both ends by steel end locks.
Leading edge constructed from rolled steel angles with
rollers.
Finish as delivered: Bright
spangled galvanised.
Consult with Northern Doors (UK) Ltd for
availability of alternative finishes.
Frame/ Guides: Side guides fixed to a fire
resistant structure of equal or greater fire resistance to that of the
shutter.
Consult with Northern Doors (UK) Ltd for recommendations and
details.
Finish as delivered: Primed for
painting.
Consult with Northern Doors (UK) Ltd for availability of
alternative finishes.
Operation:
Standard voltage: 415V, 3 phase, 50
Hz.
Control panel:
Open, close and stop buttons.
Key switch test
facility.
Connection facility to the building fire alarm system.
Audible
warning of the shutter closing.
Ironmongery: Consult with Northern Doors (UK) Ltd for recommendations
and details.
Other requirements:
Battery standby
|