Serveryfire 75
A vertical rolling fire
resistant shutter providing 1 hour fire resistance in accordance with BS 476
Part 22. Powered by a 240v 1ph electric motor, it is automatically self closing
when activated by the fire detection system.
Dimensions:
Opening height up to 2500mm, opening width up to
2500mm.
Curtain
75mmdeep cold rolled 0.9mm galvanised flat steel lath, fitted
with steel endlocks on each alternate lath to prevent lateral movement within
the curtain.
Bottom Rail
Double angle steel bottom rail, primer painted.
Side Guides
65 x 32mm cold rolled mild steel channel guides with guide
fixing angles, primer painted.
Shutter barrel
100mm diameter (minimum) x 2mm thick seamless steel
tube with and drive sprocket.
Endplates
Mild steel endplates fixed to a vertical mild steel angle by
M6 fixings, with each endplate fitted with cast steel or mild steel barrel
support cups. Primer paint finish.
Hood and motor cover
Galvanised pressed steel sheet to form 3 sided
profile coil cover, motor and drive cover.
|
Operation
Electric operation with 240v 1ph motor via standard push
button control unit. Motor with travel limits and haulchain manual override.
Auto-close via 72ºC fusible link release mechanism by gravity control
descent.
Manual option – haulchain unit in lieu of electric motor to re-open
shutter after testing. The haulchain would normally be stored at high level. The
24v DC solenoid unit auto-closing and fire door interface panel options
described below are both available with the haulchain unit.
Finish
Standard galvanised or primer paint finish. Consult with
Northern Doors (UK) Ltd for availability of alternative finishes and to obtain
samples.
Optional extras:
Electric options:
Key switch control surface
mounted.
Key switch control surface mounted.
External weatherproof push
button.
Key lockable push button station.
24v DC solenoid unit with manual
pull cord re-set to provide auto-closing of shutter with controlled descent upon
receipt of 24v DC alarm signal (by others).
24v DC solenoid unit with
electric re-set to provide auto-closing of shutter with controlled descent upon
receipt of 24v DC alarm signal (by others).
Fire door interface panel for use
in conjunction with solenoid units above, to provide audio and visual warning to
closing the shutter after variable timer. Panel provides facility to power close
the shutter, gravity close the shutter with controlled descent or close the
shutter upon mains power failure with controlled descent. And receive either 24v
DC alarm signal or volt free alarm signal, (by others).
|