Dimensions:
Self coiling push up operation - opening height up to
2800mm, opening width up to 2800mm.
Handchain/handwheel operation - opening
height up to 5500mm, opening width up to 6000mm.
Electric operation - opening
height up to 7000mm, opening width up to 7000mm.
Shutter weight: 40 kg/m² of
door opening.
Curtain
Constructed from galvanised cold rolled
interlocking curved sections of suitable gauge, each alternate lath is fitted
with a malleable steel endlock to prevent lateral movement.
Bottom
Rail
The base of the curtain is fitted with a steel angle reinforcing
rail of adequate size forming an inverted ‘T’.
Side Guides
Formed
from cold rolled mild steel channel sections secured to the opening structure by
continuous mild steel fixing angles.
Roller Assembly
Constructed
from mild steel tube,
mounted on bright steel shafts running in ball races, reduction drive gearing
where applicable is by machine cut steel gears or chain drive to suit the size
of the opening.
Endplates
The roller assembly is supported by mild
steel endplates with mounting angles for fixing to the support structure. On one
endplate, steel gears or chain drive are provided, when applicable, to provide
drive to the barrel.
Roller Enclosure (optional extra)
Formed from
galvanised pressed sheet metal to enclose the rear of the shutter barrel and
curtain assembly.
|
Electric Operation (optional extra)
A totally
enclosed reduction geared motor to suit the size of the shutter. Standard
voltage: 415V, 3 phase, 50 Hz. 240V single phase is also available. The motor is
equipped with an electromagnetic brake and limit switches. The motor position
can be handed to suit the site conditions. An emergency handchain is provided
for use in the event of a power failure.
Operation
Shutters up to a
maximum 2800mm wide x 2800mm high can be supplied self coiling push up
operation. Shutters over this size should be either mechanically geared using a
handchain or handwheel or electrically operated. Handchain operation allows the
shutter to be operated from one side only, handwheel operation allows operation
from both sides. The handchain position can be handed to suit the site
conditions.
Automatic Closing:
Fusible Link
All shutters are
supplied with a fusible link designed to close the shutter automatically when
local temperature exceeds 68°C.
Thermoelectric quartzoid bulb
An option
similar to a fusible link, which is wired into a fire alarm system (24V DC.).
Upon receipt of a signal from the fire alarm system, the bulb breaks thus
closing the shutter.
Solenoid Release
Various arrangements are available,
which when energised or de-energised, allow the shutter to self close. Normally
works on a 24V DC. circuit: further details are available on request from
Northern Doors.
Finish
All parts not galvanised are painted in one
coat of protective primer (ex works), ready for site painting by others. Powder
coat finish is available as an optional extra to BS 4800 and RAL 840 HR colour
ranges. Stainless steel 304u finish is also available.
Fire
Resistance
To BS 476: Part 22: 1987. 4 hours fire resistance (tested by
the Loss Prevention Council). LPCP Approved and certified.
|